Fire Sprinkler Head Code NFPA 25 

Is your current company following the code standards?

PER CODE – NFPA 25 ANY SPRINKLER HEAD THAT SHOWS SIGNS OF ANY OF THE FOLLOWING SHALL BE REPLACED:

• Leakage
• Corrosion**
• Physical damage
• Loss of fluid in the glass bulb
• Loading (dust or dirt) *
• Painting

* Minor dust and dirt can be blown off with canned air.
** A.5.2.1.1.2(2) – A degree of judgement should be exercised in the determination of the extent, location, and character of corrosion that would necessitate replacement.

5.2.1.1 – Sprinklers shall be inspected from the floor level annually.